Etkileşimli taslak · örnek ürünler

ETNA EDP Diesel Engine Fire Booster Control Panel

Diesel motorlu yangın hidroforu

supply voltage
12 V or 24 V DC, two battery packs
Protection class
IP65

Stock and delivery time will be confirmed in your quotation.

ETNA EDP Diesel Engine Fire Booster Control Panel

ETNA

EDP · Diesel engine fire booster

etna.EDP

Request a price quote

Quoted from the manufacturer's product page and technical manuals attached to this product.

  • Epoxy coated DKP sheet metal panel
  • Automatic manual mode selector locked button on the front cover of the panel
  • Manual start buttons and information lights on the front cover of the panel
  • IP 65 protection class
  • Ability to work with 2 group battery at 12V or 24V DC supply voltage
  • 2 built-in battery charge rectifiers for 2-battery systems
  • 180-280 VAC supply voltage for battery charge rectifiers, ability to operate at 50/60 Hz supply frequency
  • Battery voltmeter and charging current ammeter
  • Battery and charging system status information LEDs
  • Automatic start-up via pressure switches or feed tank float
  • Pressure control function
  • Automatic start with a total of 6 cycles with 2 batteries
  • 2x16 character white screen LCD
  • Ability to monitor all situations on the LCD screen
  • Ability to monitor diesel engine speed with tachometer
  • water temperature indicator
  • Oil temperature and pressure gauge
  • fuel level indicator
  • Extra manual operation buttons on the EDP panel
  • Commissioning button for testing purposes
  • Manual stop button
  • Possibility of monitoring via Modbus RTU with RS485 protocol
  • Control possibility via Modbus RTU with RS485 protocol (Start, Stop, Error reset)
  • Ability to view total, manual, test operating times and number of switches
  • Adjustable activation and deactivation delay times
  • Periyodik tämsä äääätälma feature
  • Turkish and English language option
  • Ability to keep 500 past event records in memory
  • Real time date and time
  • Automatic weekly testing on the set date, time and duration
  • Ability to restrict unauthorized access thanks to encrypted menu
  • Changeable menu password
  • Possibility of remote operation via dry contact (Start, Stop)
  • Relay dry contact outputs for motor pump active, general malfunction, low fuel level, starting error, automatic mode disabled, pump request information
  • Siren relay output for external alarm siren connection on the control panel
  • Possibility to run the engine at idle for a period of time adjustable via the throttle actuator output.
  • External alarm siren on the panel Relays Starter relays Automatic fuses Load disconnector switch Terminals Control buttons Battery chargers ETNA EDP panel

Technical specifications

Brand
ETNA
Model/configuration
EDP
Application
Diesel motorlu yangın hidroforu
Protection class
IP65
supply voltage
12 V or 24 V DC, two battery packs
Charger input
180–280 V AC, 50/60 Hz
Battery charging system
2 internal rectifiers
screen
2 × 16 character LCD
Communication
RS485, Modbus RTU
event memory
500 events
auto start
Pressure switch or feed tank float; total 6 cycles
Language options
Turkish / English

Catalogue · PDF

GÜRTES

Kurumsal bilgiler, talepleriniz ve alışveriş desteği.

Teklif İsteme Formu

Proje ve adetli ürün talepleriniz için satış departmanımızdan teklif alın.

Proje ve teknik dosya paylaşımı

Ürün kodları, miktar ve teknik gereksinimlerinizi yazın. Proje çizimi, keşif ve teknik belge ekleyebilirsiniz. Alternatif iletişim: veravira@veravira.com.

Teklif talebinizi ürün kodu ve adet bilgisiyle satış ekibimize iletebilirsiniz.

E-posta ile teklif isteSatış ekibini ara · +90 (216) 491 44 82

Bu seçenek e-posta uygulamanızı açar; site üzerinden talep kaydı oluşturmaz.